5. Maintenance 7-2018
72 A045R242 (Issue 12)Copyright © 2018 Cummins Inc.
Maintenance Item
Daily
or After
24 Hours
Weekly
or After
50 Hours
100
Hours
1 Year
or After
200 Hours
1
2
Years
1
4000
Hours
Check generator
set enclosure:
Visually check
enclosure, walk
around inspection
of generator set.
Make sure no
inlets/outlets are
covered/restricted,
service access
doors are
operational and
safety systems are
in place and
operational.
■
Check operation of
Emergency Stop
Button (where
fitted): With the
generator set
running, press the
Emergency Stop
button. Check all
systems, before
resetting the fault.
■
Replace engine oil
and filters. Refer
to the procedure in
the Engine Oil
section.
■
2
■
2
Check battery:
Check connections
to verify that they
are secure.
■ ■
Replace air
cleaner.
■
Clean radiator
core.
■
3
Check charge air
cooler for damage
and debris (where
fitted).
■