Product Manual A

5. Startup and Configuration 7-2018
70 A045R241 (Issue 13)Copyright © 2018 Cummins Inc.
Tick Item
AC and DC wires are separated in their own conduit to prevent electrical induction.
All load, line and generator connections are well made and correct.
Generator Set Pre-Start
A safety check was performed just before starting.
The generator set engine is properly serviced with oil and coolant.
The battery is properly installed, serviced and charged.
The battery charger and engine coolant heater are connected and operational, if
applicable.
All generator set covers and safety shields are installed correctly.
The fuel supply is turned on.
All fuel shutoff valves are operational.
The date and time have been set in the generator set control.
The generator set operating mode has been selected.
5.7 Startup
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables, negative (–) cable first.
After verifying that the installation was completed correctly, start and test the
system. Make sure to connect the battery cables to the battery with the positive (+)
cable first.
Read through the Operator Manual and perform the maintenance and pre-start
checks as instructed.
The following information applies to C70 N6, C80 N6, and C100 N6 generator set
models only: Adaptive learn is an engine ECM function that allows the generator set
to "learn" its environment. There are small differences in the performance of each
engine and fuel system component, so the ECM uses inputs from the engine
sensors to adjust running conditions to operate more consistently for each individual
generator set. After installation is complete and while testing the overall system
function, the generator set must be run with no active faults under load (that is,
transfer switch connected to maximum customer load available) until the engine
temperature reaches 80 °C (175 °F) to allow the adaptive learn function to initialize.