Product Manual A
4. Installation7-2018
43A045R241 (Issue 13) Copyright © 2018 Cummins Inc.
4.3 Engine Exhaust
The exhaust system for this generator set is complete and was designed specifically
for this generator set. Do not modify or add to the exhaust system of this generator
set.
WARNING
Exhaust gas is deadly. Make sure that the exhaust system terminates away
from building vents, windows, doors, and sheltered spaces that may not
have ample fresh air ventilation.
WARNING
Engine discharge air and exhaust carry carbon monoxide gas (odorless and
invisible) which can cause asphyxiation and death. Never use engine
discharge air or exhaust for heating a room or enclosed space.
4.4 Electrical Connections
WARNING
Improper installation can lead to electrocution and damage to property.
Electrical connections must be made by a licensed electrician.
WARNING
Automatic startup of the generator set during installation can cause severe
personal injury or death. Make sure the generator set is shut down and
disabled:
1. Press the generator set's "O" (Off) button to stop the generator set.
Allow the generator set to thoroughly cool to the touch.
2. Turn off and disconnect the battery charger from the AC source before
disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from
contacting the battery terminals to prevent accidental starting.
NOTICE
Refer to regional codes and the National Electrical Code (NFPA 70) for all
electrical installation requirements.
NOTICE
Class 1 wiring methods must be used for connecting the generator set.