Product Manual A

4. Installation 7-2018
30 A045R241 (Issue 13)Copyright © 2018 Cummins Inc.
No. Description No. Description
1 Cool Air In 3 Hot Air Out (Weather Enclosure)
2 Hot Air Out
FIGURE 5. EXAMPLE OF GENERATOR SET LOCATION
The generator set location is critical for safety and performance. Follow the
guidelines below:
Must comply with applicable codes (NFPA, NEC, IBC, etc.).
Use this manual for outdoor installations only. For other applications, contact
your local Cummins dealer or refer to the application manual at the following
link: http://www.cumminspower.com/www/literature/applicationmanuals/t030.pdf
Consider access to utilities, such as electric/gas meters, transfer switch, remote
fuel tank location (for liquid propane if applicable), etc.
Call the local utilities to mark the locations of buried utility services (gas,
electric, or telephone) before digging.
Verify the locations of any other buried components (gas, electric or telephone)
with the homeowner before digging.
Follow the clearance guidelines below:
The generator set must be located 5 feet from combustible materials (NFPA 37)
and any opening in a wall (window, door, vent, etc.).
The generator set must be located such that the exhaust is not able to
accumulate in an occupied area.
The generator set must have enough room for installation, service, and
maintenance.
The generator set must be located to ensure ventilation openings are not
blocked.