Maintenance Item
Daily
or After
24 Hours
Weekly
or After
50 Hours
100
Hours
1 Year
or After
200 Hours
1
2
Years
1
4000
Hours
Verify that the
coolant heater has
power and is
running (where
fitted). Check for
evidence of leaks.
Remove any
corrosion from
fittings.
■
Check engine oil
level: If low, top up
to engine
specifications
level, with
recommended oil.
■
Check fuel lines
and hoses:
Visually check for
leaks, worn or
damaged hoses.
■
Check charge
alternator: Check
visually and
audibly when the
generator set is
running.
■
Check all exhaust
components, and
hardware (fittings,
clamps, fasteners,
etc.): Visually
inspect the
exhaust system for
signs of wear or
damage. Check
audibly when the
generator set is
running.
■