Product Manual A
4. Installation 7-2018
48 A045R241 (Issue 13)Copyright © 2018 Cummins Inc.
No. Description No. Description
1 AC Distribution Connector(s)
FIGURE 12. AC ACCESSORY CONNECTIONS
The battery charger, engine coolant heater, alternator heater, CCV heater,
and battery warmer require power from a 120 VAC, 20 Amp protected circuit
from the Main Distribution Panel. Use 12 AWG 75 °C (167 °F) conductors to
make connection to the generator set AC distribution connector.
DC Connections
NOTICE
When selecting and installing conduit to the generator set, account for any