Product Manual A

4. Installation 7-2018
44 A045R241 (Issue 13)Copyright © 2018 Cummins Inc.
Electrical Preparations
1. Run all wires through a single conduit (unless prohibited by the authority having
jurisdiction).
NOTICE
Be sure to account for any needed accessories, such as a remote
display, etc.
2. Connect the conduit to the generator set. Refer to the specific outline drawing in
the Outline and System Drawings section for the size and location of the hole
provided for electrical conduit connection. The existing hole may be increased
in size to match conduit used.
AC Connections
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables, negative (–) cable first.
NOTICE
If a 100% rated breaker is used, 90 °C wire must be used for L1, L2, and L3
with the wire size determined by the 75 °C ampacity tables.
NOTICE
When using a circuit breaker with an adjustable, electronic trip unit, the
amperage and trip curve settings may need adjustment to match the
generator set load wiring, or downstream loads and circuit breakers. An
accessory seal kit (part number A026M166) is available to tamper-proof the
adjustable settings.
1. Make sure the generator set is shut down and disabled:
a. Press the Off switch from the display and then press the E-Stop button to
stop the generator set. Allow the generator set to thoroughly cool to the
touch.
b. Turn off and disconnect the battery charger from the AC source before
disconnecting the battery cables.
c. Disconnect the negative (–) cable from the battery and secure it from
contacting the battery terminals to prevent accidental starting.
2. Remove the enclosure side panel to access the main circuit breaker box.
3. Place the circuit breaker handle in the OFF position.