Product Manual A
4. Installation 7-2018
34 A045R241 (Issue 13)Copyright © 2018 Cummins Inc.
NOTICE
A shutoff valve is recommended and often required by local and state codes.
Natural Gas Fuel System
Requirements for a natural gas generator set are as follows:
TABLE 15. NATURAL GAS GENERATOR SET REQUIREMENTS
Component Description
Gas Pipeline quality
Fuel Supply Adequate fuel supply to operate correctly and run at full load
Shutoff Valve Manual
Fuel Pipe Size The length of the fuel supply pipe from the gas service entrance to the
generator set must be known to determine the correct fuel pipe size.
Refer to the charts in the Fuel Line Selection appendix.
Iron pipe must be a minimum of Schedule 40 subject to the authority
having jurisdiction.
Flexible Fuel Line Attached to the radiator guard. Protects the fuel system from vibration,
expansion, and contraction.
WARNING
Fuel leaks can lead to explosive accumulations of gas. Prevent gas leaks
and the accumulation of gaseous fuel in the event of a leak.