Product Manual A

4. Installation7-2018
33A045R241 (Issue 13) Copyright © 2018 Cummins Inc.
Gaseous-fuel supply system design, materials, components, fabrication, assembly,
installation, testing, inspection, operation, and maintenance must comply with the
applicable codes. See NFPA Standards No. 37, 54, and 58. If this is a seismic
installation, refer to IBC codes and standards. Where seismic installation is
required, there may be specific anchorage requirements for the generator set and
other installed components.
Most codes require a manual shutoff valve ahead of a flexible fuel hose. The
generator set includes electric (battery-powered) shutoff valves.
NOTICE
It is recommended that a shutoff valve be located near the generator set for
emergency shut off or servicing the generator set. Follow applicable codes.
Until the generator set is connected, cap the fuel line stub-up at the generator set to
prevent dirt from entering and gas from discharging if the gas supply shutoff valve is
opened accidentally.
To determine the required capacity, refer to the Fuel Line Selection section.
Fuel Line Connections
WARNING
Fuel presents the hazard of fire or explosion that can result in severe
personal injury or death. Do not smoke or allow any flame, spark, pilot light
or other ignition sources near fuel or in the installation area. Read the
important safety precautions in this manual.
1. Refer to the Outline and System Drawings appendix for the location of the fuel
supply connection through the side of the generator set.
2. Install a flexible fuel hose, which must be used between the engine's fuel
system and fuel supply line to protect the fuel system from damage caused by
vibration, expansion and contraction. The fuel hose must be installed according
to all applicable codes and standards.
Installing Fuel Lines
The basic components required for fuel line installation are as follows:
Flexible fuel line (attached to the radiator guard)
Fuel line
Shutoff valve
Fuel supply
To install the fuel lines:
1. Connect a flexible fuel line to the fuel connection ports on the generator set.
2. Connect the opposite end of the flexible fuel line to the fuel source line near the
shutoff valve.