Product Manual
3. Installation 8-2018
28 A056K730 (Issue 4)Copyright © 2018 Cummins Inc.
No. Description No. Description
1 Ground Lugs 3 Extra Ground
2 Bonding Jumper
FIGURE 20. MAIN BONDING JUMPER
3.1.5 Mounting Method
RA Series transfer switches are mounted to a wall. Follow the appropriate set of mounting instructions and
refer to the outline drawings in Appendix C for installation dimensions, specifications, and mounting hole
patterns. Enough room must be allowed to remove the door panel for inspection and servicing of the
switch, as per NEC and local codes.
3.1.5.1 Wall Mounting
1. Make sure that the wall where the transfer switch is to be mounted is suitable to hold firmly the
weight and size of the transfer switch, within a reasonable safety factor.
2. Check the location to be sure that no wires or plumbing, gas, or exhaust lines run behind the wall.
NOTICE
For Service Entrance models with integrated circuit breakers, the National Electric Code
stipulates that the installed height of the circuit breaker selector switch is not more than 6 ft
7 in. above the floor, grade, or platform.
3. Make sure that the anchorage fasteners used to bolt the switch to the wall are strong enough to
withstand the switch weight and its vibration during operation, within a reasonable safety factor.
4. Use four 1/4 inch bolts for wall mounting. Measure and mark the wall for drilling.
5. Install two mounting bolts in the wall for the top cabinet mounting keyholes.
6. With the shipping box standing so that the cabinet is lying down, carefully remove the top and the
foam from the box.