Product Manual
3. Installation8-2018
23A056K730 (Issue 4) Copyright © 2018 Cummins Inc.
NOTICE
Service entrance (SE) model transfer switches are rated service entrance equipment. The main
bonding jumper is factory installed in the connected position between the Neutral assembly and
Ground stud on the cabinet. By installing a transfer switch as shown in the figure below, the
main bonding jumper should be removed or moved from a connected position to a disconnected
position
No. Description No. Description
1 Utility Source 6 Circuit Breaker
2 Utility Panel 7 Generator Source
3 Loads 8 Loads
4 Circuit Breaker 9 Distribution Panel
5 Transfer Switch
FIGURE 15. PARTIAL COVERAGE SYSTEM (SERVICE ENTRANCE MODEL)