Product Manual B

3. Wiring5-2019
230962-0617 (Issue 8) Copyright © 2019 Cummins Inc.
No. Description No. Description
1 GND 5 Remote Test
2 2 6 Transfer Inhibit
3 B+ 7 Retransfer Inhibit
4 RMT 8 Common
FIGURE 14. TB2 CONNECTIONS FOR RETRANSFER INHIBIT
NOTICE
TB1 and TB2 will accept 22 AWG - 12 AWG wire with 3/8 inch strip (10 mm). Torque to 9 in-lbs.
3.2.7 Remote Override Input
To add remote override, connect a normally open, dry contact between P4-2 on the back of the control
panel and TB2-8. Closing the contact enables the feature and opening the contact disables it.