Product Manual B

3. Wiring5-2019
210962-0617 (Issue 8) Copyright © 2019 Cummins Inc.
No. Description No. Description
1 GND 5 Remote test
2 2 6 Transfer inhibit
3 B+ 7 Retransfer Inhibit
4 RMT 8 Common
FIGURE 12. TB2 CONNECTIONS FOR REMOTE TEST TRANSFER
NOTICE
TB1 and TB2 will accept 22 AWG - 12 AWG wire with 3/8 inch (10 mm) strip. Torque to 9 in-lbs.
3.2.5 Transfer Inhibit Input
To add transfer inhibit, connect a normally open, dry contact between terminals 6 and 8 of TB2. Closing
the contact enables the feature and opening the contact disables it.