Product Manual A
5. Control Panel Configuration11-2017
910962-0131 (Issue 6) Copyright © 2017 Cummins Inc.
5.2.12 System Nominal Frequency 50/60 Hz
Function Function Code Function Code Value
**System Nominal Frequency 50/60 Hz 60 Hz
50 Hz
5.2.13 Single Phase/Three Phas e
Function Function Code Value Code Value
**Single Phase/Three Phase Three Phase
Single Phase
5.2.14 Utility Under-Volt a ge Pickup
Function Function Code Value Code Value
(Default)
Utility Under-voltage Pickup (90%)
95%
5.2.15 Utility Under-Volt a ge Dropout
Function Function Code Value Code Value
(Default)
Utility Under-voltage Dropout 90%
(85%)
80%
70%
5.2.16 Phase Check On/Off
Function Function Code Value Code Value
(Default)
Phase Check On/Off (Off)
On