Product Manual A
5. Control Panel Configuration11-2017
870962-0131 (Issue 6) Copyright © 2017 Cummins Inc.
5.2.1 Not Available
Function Function Code Value Code Value
(Default)
Not Available N/A
5.2.2 Time Delay Engine Start (TDES)
Function Function Code Value Code Value
(Default)
TDES
(Time Delay Engine Start)
0 Seconds
(Disabled)
0.5 Second
1 Second
2 Seconds
(3 Seconds)
4 Seconds
6 Seconds
10 Seconds
5.2.3 Time Delay Normal to Emergency (TDNE)
Function Function Code Value Code Value
(Default)
TDNE
(Time Delay Normal to Emergency)
0 Seconds
(Disabled)
1 Second
2 Seconds
3 Seconds
(5 Seconds)
30 Seconds
120 Seconds
300 Seconds