810962-0131 (Issue 6) Copyright © 2017 Cummins Inc.
6. Press the OK button to display the PIN Number menu.
NOTICE
If you choose not to enter a 4-digit access code at this time, the only way to exit Manual
mode is to press the reset (Res) button.
7. Press the + or - buttons to enter the first digit of your 4-digit access code.
8. Press the OK button. Then press the + or - buttons to enter the second digit of your 4-digit access
code.
9. Repeat step 8 for the third and fourth digit of your 4-digit access code.
10. Press the OK button. The Home menu is then redisplayed.
4.7.12 After Programming the Exerciser Clock
1. Make sure the External Exercise function on the transfer switch control panel is set to “On."
2. Place the generator set operation selector switch in the Remote position.
3. Check the system for proper operation as described in the Operator's Manual.
4.7.13 Resetting the Timer
The Reset button should only be used in cases of an emergency. Resetting the timer erases all existing
language, date, and time settings. Upon pressing the Res button, the clock is set to 12:00 midnight,
Wednesday, January 1, 2003. However, scheduled exercise periods remain intact.
1. Use a pointed object to press the Res button for approximately one second. Two information screens
are displayed and the default national language is flashed.