The following image illustrates how the pickup and dropout settings work.
4.4.1.1 Utility Under-Voltage Set Points
NOTICE
If the utility under-voltage pickup is set at 90%, then the dropout has to be set lower than 90%.
TABLE 3. UTILITY UNDER-VOLTAGE SET POINTS
Description Available Set Points
Under-voltage Pickup
(% of Nominal)
95%
90%
Under-voltage Dropout
(% of Nominal)
90%
85%
80%
70%
4.4.1.2 Under-Voltage Sensing
No. Description No. Description
1 Drop-out setting (204V) 4 Volts
2 Pick-up setting (216V) 5 85% of Nominal
3 Nominal set point (240V) 6 90% of Nominal
4.4.2 Generator Sensor
The generator sensor is a single phase sensor that monitors under-voltage and under-frequency
conditions. All the pickup and dropout settings are fixed and are not adjustable. The generator set under-
voltage and under-frequency set points are listed in the following table.