4 Operation
4.1 Transfer Switch Configuration
The transfer switch is preset at the factory to operate using default settings. The control will operate the
transfer switch when power is applied. However, you may wish to adjust some of the settings for your
application.
The transfer switch must be installed correctly, with DC power present, before any adjustments to the
configuration can be made. If the transfer switch is connected to utility power, the Utility Power Connected
LED will be lit if battery power is available. Utility or genset voltage need not be present to adjust the
configuration.
The following tables show which control functions should not be changed and which functions can be
changed for your application.
TABLE 1. FUNCTIONS PRESET AT THE FACTORY THAT SHOULD NOT BE CHANGED
Function Factory Setting
System Nominal Voltage Table Set for your system voltage
System Nominal Voltage Set for your system voltage
System Nominal Frequency Set for your system frequency
System Phase Set for your system
External Exercise Set to “On" if the external exerciser option was ordered; otherwise, set to
“Off"
TABLE 2. FUNCTIONS THAT CAN BE CHANGED
Function Factory Setting
TDES (Time Delay Engine Start) 3 Seconds
TDNE (Time Delay Normal to Emergency) 5 Seconds
TDEN (Time Delay Emergency to Normal) 10 Minutes
TDEC (Time Delay Engine Cool-down) 10 Minutes
TDPT (Time Delay Programmed Transition) 0 Seconds
TDEL (Time Delay Elevator Signal) 0 Seconds
Test With or Without Load Without Load
Exercise With or Without Load Without Load
Utility Under-voltage Pickup 90%
Utility Under-voltage Dropout 85%
Phase Check Off
Return to Programmed Transition Off
Elevator Post Transfer Delay Off