Product Manual A

3. Description11-2017
210962-0131 (Issue 6) Copyright © 2017 Cummins Inc.
This LED flashes once per second if there is a failure to connect to or disconnect from the genset, when
commanded. The control makes five attempts (there is ten seconds between each attempt) to connect to
or disconnect from the genset before it flashes the failure.
Test: This amber LED is lit when there is an active test period. This LED flashes twice per second when
the Test pushbutton is pressed to set or cancel a test period.
Exercise: This amber LED lights when repeat exercise periods have been set. This LED flashes twice per
second when the Set Exercise pushbutton is pressed to set or cancel an exercise. This LED flashes once
per second during an active exercise period.
3.6.3 Membrane Pushbuttons
The control panel includes three membrane pushbuttons.
Test: The Test pushbutton is used to set or cancel a test period. The control can be configured to test the
genset with or without load.
NOTICE
The Test pushbutton is also used in the Configuration Mode to step through the function codes.
Override: The Override pushbutton is used to terminate or bypass some time delays, to stop the Power
Connected LEDs from flashing as a result of a failure to connect to or disconnect from a power source and
to cancel an active exercise period.
NOTICE
The Override pushbutton is also used in the Configuration Mode to step through the value codes.
Set Exercise: The Set Exercise pushbutton is used to set or cancel repeat exercise periods using the
integrated exerciser.