Product Manual A
3. Description11-2017
190962-0131 (Issue 6) Copyright © 2017 Cummins Inc.
No. Description No. Description
1 GND 5 Remote Test
2 2 6 Transfer Inhibit
3 B+ 7 Retransfer Inhibit
4 RMT 8 Common
FIGURE 11. CONNECTIONS FOR REMOTE OVERRIDE INPUT
NOTICE
TB1 and TB2 will accept 22 AWG - 12 AWG wire with 3/8 inch strip (10 mm). Torque to 9 in-lbs.
3.6 EC Control Panel
The EC control panel is located on the cabinet door.
The control features are divided into three groups:
• Control Function LEDs
• ATS Status LEDs
• Membrane Pushbuttons
3.6.1 Control Function LEDs
The control panel includes eight LEDs that display codes that indicate various control functions that can
be configured. The first five LEDs display the function code and the last three LEDs display the value code
for the displayed function.
With the exception of the first LED (Test), normally these LEDs are off and are only lit when in
Configuration Mode. The Test LED is also used to notify the user of test periods.