Product Manual A

3. Description 11-2017
18 0962-0131 (Issue 6)Copyright © 2017 Cummins Inc.
No. Description No. Description
1 Reset button 3 LED status indicator
2 Digital display
FIGURE 10. 2-AMP BATTERY CHARGER CONTROL PANEL
3.5.1.2.2 2-Amp Battery Charger Configuration
The RESET button on the control panel is used to configure the battery charger for the correct battery
voltage. (More information on Setup menus is included in the Battery Charger Operator Manual.)
3.5.2 Auxiliary Relays Option
Auxiliary relays provide contacts for energizing external alarms, remote indicators and control equipment
such as louver motors and water pumps.
All relays have two normally open and two normally closed contacts that are rated for 10 Amps at 600
VAC. Connections to the auxiliary relays are made directly to the relay terminals.
There are two types of auxiliary relay coils:
12 VDC
24 VDC
3.5.3 Remote Override Input
To add remote override, connect a normally open, dry contact between P4-2 on the back of the control
panel and TB2-8. Closing the contact enables the feature and opening the contact disables it.