Product Manual A
3. Description 11-2017
14 0962-0131 (Issue 6)Copyright © 2017 Cummins Inc.
No. Description No. Description
1 GND 5 Remote test
2 2 6 Transfer inhibit
3 B+ 7 Retransfer inhibit
4 RMT 8 Common
FIGURE 6. TB2 CONNECTIONS FOR RETRANSFER INHIBIT
3.5 Options
3.5.1 Battery Charger Options
Two battery chargers are available. One battery charger is rated for 2 amperes at 12 or 24 VDC. The
other battery charger is rated for 15 amperes at 12 VDC or 12 amperes at 24 VDC.
A float-charge battery charger regulates its charge voltage to continuously charge without damage to the
battery. As the battery approaches full charge, the charging current automatically tapers to zero amperes
or to steady-state load on the battery.
3.5.1.1 15/12-Amp Battery Charger
There are two types of 15/12-amp PowerCommand battery chargers. All 15/12-amp battery chargers have
a 20 amp DC circuit breaker switch on the bottom of the battery charger.
• The 120, 208, and 240 VAC battery chargers include:
◦ Two 10-Amp AC circuit breaker switches
◦ A circuit breaker guard
• The 277, 380, 416, and 600 VAC battery chargers include:
◦ Two AC fuse holders