Product Manual A

70962-0131 (Issue 6) Copyright © 2017 Cummins Inc.
3 Description
3.1 Cabinet
Cabinets are available in various configurations that meet UL and National Electrical Manufacturer's
Association (NEMA) requirements. Each cabinet includes an identification label. The standard cabinet
offerings are:
Type 1 Indoor - general purpose
Type 3R Outdoor - rainproof
Type 4 Outdoor - watertight
Type 4X Outdoor - watertight, stainless steel
Type 12 Indoor - dust tight
3.2 Transfer Switch Components
The transfer switch opens and closes the contacts that transfer the load between the power sources
(Source 1 and Source 2). The switch is mechanically interlocked to prevent simultaneous closing to both
power sources (except in switches capable of closed transitions).
3.2.1 Contact Assemblies
The automatic transfer switch has either three or four poles. Three pole transfer switches are provided
with a neutral bar. The contact assemblies make and break the current flow. When closed to either power
source the contacts are mechanically held. A mechanical interlock prevents them from closing to both
power sources at the same time.
3.2.2 Linear Actuator
The linear actuator moves the contact assemblies between the contacts of both power sources. Linear
actuator operation is initiated automatically by the transfer switch control. Manual operation of the switch is
also possible.
3.2.3 Auxiliary Contacts
Auxiliary contacts are provided on the utility and genset sides of the transfer switch. They are actuated by
operation of the transfer switch during transfer and retransfer. The utility auxiliary contact switch is
actuated when the transfer switch is connected to the utility. The genset auxiliary contact switch is
actuated when the transfer switch is connected to the genset. The auxiliary contacts have current ratings
of 10 amperes at 250 VAC. The contacts are wired to terminal block TB1.