Product Manual A
2. Introduction11-2017
50962-0131 (Issue 6) Copyright © 2017 Cummins Inc.
2.5 Specifications
2.5.1 Model OTEC
Transfer Switch Model OTEC Specifications:
Model Amps Cabinet Types Util-to-Gen Gen-to-Gen Util-to-Gen & Util-
to-Util
Transfer
Modes
OTECA 40
70
125
All Amps:
1, 3R, 4, 4x, 12 X
OT
PT
OTECB 150
225
260
All Amps:
1. 3R, 4, 4x, 12 X
OT
PT
OTECC 300
400
600
All Amps:
1, 3R, 4, 4x, 12 X
OT
PT
OTECD 800
1000
All Amps:
1, 3R, 4, 4x, 12
X
OT
PT
2.6 Automatic Transfer Switch Typical Function
Automatic transfer switches perform the basic function of transferring the load to the available power
source. The controller monitors each source for allowable voltage and frequency range.
The transfer switch(es) identified on the cover of this manual are designed for each, all or a combination
of the following applications (If you are unsure which of these your transfer switch uses, refer to the
Specifications section of this manual):
2.6.1 Open Transition with Sync Check
Open transition with sync check executes an open transition (OT) transfer when both sources of power
are within specified tolerances of frequency, voltage and relative phase difference. If both sources meet
the tolerances, a fast transfer occurs.
2.6.2 Programmed Transition
Programmed transition executes a programmed transition (PT) transfer by disconnecting the load from the
source of power, pausing in the neutral position of the transfer switch (between switched positions) to
allow transient voltages from the load to diminish, and then the load is switched to the other source.
2.7 Utility-to-Generator Set Operation
In utility-to-generator set applications, the transfer switch performs the following functions:
1. Senses the interruption of the Source 1 power (Utility).
2. Sends a start signal to the generator set (Source 2).
3. Transfers the load to the Source 2 power.
4. Senses the return of Source 1 (Utility).