Spec Sheet
power.cummins.com
©2017 Cummins Power Generation Inc. | DS44g-CPGK A055S601 (02/17)
Generator set specifications
Model C60 D6 C80 D6C C100 D6C C125 D6D C150 D6D C175 D6D C200 D6D
Controller PowerCommand 1.1
Operating temp. range -40° F to +122° F
Circuit Breaker 250 400 * 600* 600 * 800 * 800 * 800 *
Governor reg. class ISO 8528 Part 1 Class G3
Voltage regulation, no
load to full load
± 1.0%
Random voltage variation ± 1.0%
Frequency regulation Isochronous
Random freq. variation ± 0.5%
Radio frequency
emissions compliance
FCC code title 47 part 15 class A and B
* - Indicates that circuit breaker is adjustable
Engine specifications
Model C60 D6 C80 D6C C100 D6C C125 D6D C150 D6D C175 D6D C200 D6D
Design QSB3.3 QSB5 QSB7
Displacement
3.26 L
(199 in
3
)
4.5 L (272 in
3
) 6.69 L (408 in
3
)
Cylinder block Cast iron, in-line
Battery capacity
(at ambient temperature
of 0 °C (32 °F))
850 amps 2x 850 amps
Battery charging
alternator
50 amps 100 amps 100 amps
Starting voltage 12-volt, negative ground 2x 12-volt, negative ground
Lube oil filter type(s) Spin-on with relief valve
Standard cooling system High ambient radiator
Rated speed 1800 rpm
Alternator specifications
Model
C60 D6 C80 D6C C100 D6C C125 D6D C150 D6D C175 D6D C200 D6D
Design Brushless, 4 pole, drip proof, revolving field
Stator 2/3 pitch
Rotor Direct coupled, flexible disc
Insulation system Class H per NEMA MG1-1.65
Standard temp. rise 120 ºC (248 °F) Standby
Exciter type Torque match (shunt) with PMG as option
Alternator cooling Direct drive centrifugal blower
AC waveform Total
Harmonic Distortion
(THDV)
< 5% no load to full linear load, < 3% for any single harmonic
Telephone Influence
Factor (TIF)
< 50 per NEMA MG1-22.43
Telephone Harmonic
Factor (THF)
< 3%