Service Manual
Table Of Contents
- Table of Contents
- 1. IMPORTANT SAFETY INSTRUCTIONS
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 Generator Set Safety Code
- 1.4 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.5 Fuel and Fumes Are Flammable
- 1.6 Exhaust Gases Are Deadly
- 1.7 The Hazards of Carbon Monoxide
- 1.8 Earth Ground Connection
- 2. Introduction
- 3. Startup
- 4. Operation
- 5. Maintenance
- 5.1 Maintenance Safety
- 5.2 Periodic Maintenance
- 5.3 Engine Oil
- 5.4 Engine Valve Clearance
- 5.5 Normal Duty Air Cleaner Element Replacement
- 5.6 Exhaust System Maintenance
- 5.7 DC Electrical System
- 5.8 Batteries
- 5.9 Spark Plugs
- 5.10 Cleaning the Generator Set Housing
- 5.11 Cleaning the Slip Rings
- 5.12 Exercising the Generator Set
- 5.13 Complete System Test
- 6. Service
- 7. Troubleshooting
- 7.1 Troubleshooting Procedures
- 7.2 Safety Considerations
- 7.3 GATRR Troubleshooting Approach
- 7.4 Tools and Parts Required
- 7.5 Troubleshooting with the Local or Remote Displays
- 7.6 Utility-Powered Battery Charger Troubleshooting
- 7.7 Engine Flywheel Battery Charger Troubleshooting
- 7.8 Fuel Shutoff Solenoid Valve
- 7.9 Compression Test Procedure
- 7.10 Connecting with the InPower Service Tool
- 7.11 Troubleshooting by Symptom
- 7.12 Troubleshooting with Fault Codes
- 7.13 Remote Monitoring Communication Troubleshooting
- Appendix A. Wiring Diagrams
6. Service 10-2019
90 A062J683 (Issue 1)Copyright © 2019 Cummins Inc.
WARNING
Automated Machinery
When the generator set is in Remote mode, it may start unexpectedly.
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Because any display configured as “Local” can enable the generator set’s
Remote mode, make sure that only the display located at the generator set is
configured as “Local”.
To access the HMI Type screen:
1. From the Main screen, select Menu.
2. Press and hold the NEXT key down for at least 5 seconds to view the Config
Menu.
3. Use the arrow keys to highlight "HMI Type" and click the Enter key. The HMI
Type screen appears.
4. In the Display field, select Local or Remote.
5. Keep selecting the Back button to save the settings and return to the Main
screen.