Service Manual
Table Of Contents
- Table of Contents
- 1. IMPORTANT SAFETY INSTRUCTIONS
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 Generator Set Safety Code
- 1.4 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.5 Fuel and Fumes Are Flammable
- 1.6 Exhaust Gases Are Deadly
- 1.7 The Hazards of Carbon Monoxide
- 1.8 Earth Ground Connection
- 2. Introduction
- 3. Startup
- 4. Operation
- 5. Maintenance
- 5.1 Maintenance Safety
- 5.2 Periodic Maintenance
- 5.3 Engine Oil
- 5.4 Engine Valve Clearance
- 5.5 Normal Duty Air Cleaner Element Replacement
- 5.6 Exhaust System Maintenance
- 5.7 DC Electrical System
- 5.8 Batteries
- 5.9 Spark Plugs
- 5.10 Cleaning the Generator Set Housing
- 5.11 Cleaning the Slip Rings
- 5.12 Exercising the Generator Set
- 5.13 Complete System Test
- 6. Service
- 7. Troubleshooting
- 7.1 Troubleshooting Procedures
- 7.2 Safety Considerations
- 7.3 GATRR Troubleshooting Approach
- 7.4 Tools and Parts Required
- 7.5 Troubleshooting with the Local or Remote Displays
- 7.6 Utility-Powered Battery Charger Troubleshooting
- 7.7 Engine Flywheel Battery Charger Troubleshooting
- 7.8 Fuel Shutoff Solenoid Valve
- 7.9 Compression Test Procedure
- 7.10 Connecting with the InPower Service Tool
- 7.11 Troubleshooting by Symptom
- 7.12 Troubleshooting with Fault Codes
- 7.13 Remote Monitoring Communication Troubleshooting
- Appendix A. Wiring Diagrams
5. Maintenance10-2019
85A062J683 (Issue 1) Copyright © 2019 Cummins Inc.
2. Place the generator set in Standby mode.
3. Switch the main utility disconnect from the ON to the OFF position.
4. Make sure the following occurs:
a. The generator set starts.
b. After the generator set starts and stabilizes, the load is transferred from the
utility to the generator set.
5. Switch the main utility disconnect from the OFF to the ON position.
6. Make sure the following occurs:
a. After approximately 5 minutes, the load is transferred back to the utility.
b. Once the transfer switch is connected to utility power, after approximately 5
minutes, the generator set stops.
NOTICE
If the test fails, call your authorized Cummins service provider to fix the
problem.