Service Manual

Table Of Contents
2. Introduction10-2019
17A062J683 (Issue 1) Copyright © 2019 Cummins Inc.
RA Series Automatic Transfer Switch Owner Manual (A046S594) (models
RA112N3, RA212N3, RA112S3, RA212S3, RA412N3, and RA412S3) - if
applicable
Parts Manual (A053X179)
Standard Repair Times - HO Family (A053X186)
Service Tool Manual (A043D529)
Warranty Failure Code Manual (F1115C)
Engineering Application Manual T-030: Liquid Cooled Generator Sets
(A040S369)
2.5 Model Specifications
TABLE 1. MODEL VARIATIONS
Model
Natural Gas or
Propane Vapor
kW Amps Frequency Voltage
C13N6H Both 13 54.2
60 Hz
120/240 VAC
Single Phase
C17N6H Both 17 70.8
C20N6H,
C20N6HC
Natural Gas Only 18 75
Propane Vapor
Only
20 83.3
NOTICE
Maximum load imbalance allowed is 50% of generator set rating.
TABLE 2. COLD WEATHER REQUIREMENTS
Temperature Description
Above 4 °C (40 °F) No starting aids required
–17 to 4 °C (0 to 40 °F) Alternator heater
Below –17 °C (0 °F)
Alternator heater
0W30 oil (see the oil recommendation below)
Extreme cold weather kit (A054B984) (includes battery and
oil heaters)