d. Inspect the spark plugs for damage and proper gap:
Remove and inspect spark plugs. If they are damaged or dirty, replace
them.
Measure the spark plug gap. Re-gap if necessary.
18. Measure temperature of the air intake and temperature rise across the
generator set.
Remove the blockage or prevent air recirculation as necessary.
Code 37 - Invalid Set Configuration
Logic: Generator set control configuration does not meet any valid configuration.
Possible Causes:
Generator set configuration
Control
Diagnosis & Repair:
1. Check the last fault recorded.
If this fault has not been repaired, troubleshoot that fault.
2. Using the display, reset and save the generator set configuration. See the
instructions in the "Generator Config" Screen section.
3. If the generator set configuration is correct and the fault will not clear, replace
the control.
Code 43 - Processor Fault
Logic: RAM (programming variables) error during self-test
Possible Causes: Faulty program
Diagnosis & Solution:
1. Check the last fault recorded.
If this fault has not been repaired, troubleshoot that fault.
2. Replace the control as necessary.
Code 45 - Speed Sense Fault
Logic: While running, the quadrature frequency dropped to 0 Hz for 1 continuous
second
Possible Causes:
Loads
Alternator windings
Wire connections
Open or corroded slip rings and brushes