Quick Start Installer

A062M459 (Issue 2) 7-2019 Page 2 of 6 Copyright © 2019 Cummins Inc.
Generator Set Mounting Pad Checklist
The earth on which the generator set mounting pad rests is strong enough and will not allow shifting or movement.
Observe local codes on soil bearing capacity.
The generator set is properly supported and attached to an approved base.
The supporting base is non‐combustible and is at least as large as the generator set base.
The generator set is located to comply with applicable codes and standards.
Generator Set Size (All Models) Generator Set Weight (Including Battery)
Dimension
L x W x H
Note: Refer to the installation manual for stubup locating dimensions.
Generator Set Support Checklist
The floor, roof or earth on which the generator set rests is strong enough and will not allow shifting or movement. Local
codes for soil bearing capacity were followed.
The generator set is properly supported and secured to an approved base.
The supporting base is of non‐combustible material and extends 2 inches (50.8 mm) all around the generator set.
FUEL
Note: Incorrect fuel line sizing and regulation are the most common reasons that generator sets do not perform as designed.
Refer to installation
manual for instructions on properly sizing the generator set fuel line.
Typical System Components
Natural Gas
No.
Description
No.
Description
1
Distance as Required by Code and/or Component Suppliers
6
Full Flow Manual Shutoff Valve
2
Primary Service Pressure Regulator
7
Secondary Service Pressure Regulator (if Required)
3
Natural Gas Supply
8
Flexible Fuel Line
4
Gas Meter
9
Sediment Trap
5
Note: A branch in the fuel line to the generator set may allow
selection of a
smaller diameter line size to the generator set
and remainder of gas appliances.
10
Fuel Line Connection at Generator Set
11 Generator Set
Models
kg
lbs
C13N6H
218
479
C17N6H, C20N6H
241
531