6. Troubleshooting8-2019
89A062J680 (Issue 2) Copyright © 2019 Cummins Inc.
• Ignition
• Wire connections
Diagnosis and Repair:
1. Reduce the number of connected loads especially loads that require higher
starting current, such as air conditioners.
2. Have the unit serviced by an authorized Cummins dealer.
Code 19 - Governor Actuator Shutdown
Possible Causes:
• Governor actuator
• Wire connections
Corrective Action:
1. Have the unit serviced by an authorized Cummins dealer.
Code 22 - Governor Actuator Overload
Possible Causes:
• Air fuel mixture
• Fuel supply
• Exhaust system
• Generator set loads
• Governor actuator
• Ignition system
• Wire connections
Corrective Actions:
1. Reduce the number of connected loads especially loads that require higher
starting current such as air conditioners.
2. Check and service air filter as necessary.
3. Have the unit serviced by an authorized Cummins dealer.
Code 27 - Voltage Sense Lost
Possible Causes:
• Alternator windings
• Generator set loads
• Ignition
• Wire connections
Corrective Action:
1. Have the unit serviced by an authorized Cummins dealer.