Product Manual

5. Maintenance8-2019
79A062J680 (Issue 2) Copyright © 2019 Cummins Inc.
6. Re-install the access panel and tighten the screws. Torque 3.5 - 5.0 ft-lb (5.0 -
6.6 Nm).
7. Reconnect the battery and restore the original generator set settings.
5.5 Batteries
Batteries are an essential part of any standby generator set system. A significant
amount of generator set failures are due to battery issues.
It is therefore vital that batteries are stored, commissioned, and maintained as
detailed here. Reference should also be made to the battery manufacturer’s
instructions.
Maintenance free batteries (if supplied with the generator set) need no maintenance
for commissioning.
Storage
Batteries must be stored in a cool, dry, well-ventilated place, in the upright position,
and with the vent caps securely in place.
Batteries must never be stacked on top of each other and must be protected from
the floor by a wooden pallet or suitably thick cardboard sheet.
Safety Precautions
Servicing of batteries are to be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
General Precautions for Maintenance-Free Batteries
Handling and proper use of batteries is not hazardous if the correct
precautions are observed and personnel are trained in their use.
WARNING
Arcing Hazard
Laying tools or metal objects across the battery can cause arcing that
may ignite battery gases causing explosions resulting in personal
injury.
Never lay tools or metal objects across the top of the battery.
WARNING
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can
cause severe burns or death.
Use tools with insulated handles to prevent the risk of electric shock.