Product Manual
Table Of Contents
- Table of Contents
- 1. IMPORTANT SAFETY INSTRUCTIONS
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 Generator Set Safety Code
- 1.4 Moving Parts Can Cause Severe Personal Injury or Death
- 1.5 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.6 Fuel and Fumes Are Flammable
- 1.7 Batteries Can Explode
- 1.8 Exhaust Gases Are Deadly
- 1.9 The Hazards of Carbon Monoxide
- 1.10 Earth Ground Connection
- 2. Introduction
- 3. Control System
- 4. Operation
- 5. Maintenance
- 6. Troubleshooting
5. Maintenance 8-2019
74 A062J680 (Issue 2)Copyright © 2019 Cummins Inc.
5. When a sufficient amount of oil has been drained from the system, close
the drain valve at the engine and the oil drain cap on the hose.
6. Wipe the oil drain cap clean.
7. Re-install the access panels. Torque the fasteners 5.0–6.6 Nm (3.5– 5.0
ft-lb).
8. Dispose of the used oil in accordance with local and state regulations.
Changing Engine Oil and Oil Filter
NOTICE
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables, negative (–) cable first.
WARNING
Toxic Hazard
State and federal agencies have determined that contact with used engine oil
can cause cancer or reproductive toxicity.
Avoid skin contact and breathing of vapors. Use rubber gloves and wash
exposed skin.
NOTICE
If the oil and/or oil filter are not reused, dispose of them in accordance with
local environmental regulations.
NOTICE
Change the engine oil and filter when the generator set is not running and is
out of Remote mode.
NOTICE
Change the oil more often in hot and dusty environments.
NOTICE
Cummins highly recommends that any service or maintenance work be
performed by qualified technicians.
1. Open the generator set's circuit breaker to prevent the ATS from transferring to
generator set source when manually starting.
2. Before changing the oil, manually start the generator set.
3. Allow the generator set to run for 2 to 5 minutes to warm the engine oil.