3. Control System 8-2019
32 A062J680 (Issue 2)Copyright © 2019 Cummins Inc.
• Bimonthly: will exercise the generator set on the first and third occurrence
of the selected day every month
• Monthly: will exercise the generator set on the first occurrence of the
selected day every month
• Never: will never exercise the generator set
Select the Next key to go to the date and time fields.
6. Use the arrow keys to set the day and time the generator set will be exercised.
Select the Next key to highlight the Exercise Now field.
7. Select either arrow key to start the Exercise Now function.
NOTICE
Initiating the Exercise Now function will cause the generator set to start
immediately and run for the amount of time indicated by the Exercise
Time field, or run the Crank Exercise sequence. The ATS does not
transfer to generator power during exercise mode. Normally scheduled
exercise events will occur after the completion of the immediate exercise
event.
8. Keep selecting the Back button to save the settings and return to the Main
screen.