Product Manual

2. Introduction8-2019
15A062J680 (Issue 2) Copyright © 2019 Cummins Inc.
Warranty Failure Code Manual (F1115C)
Engineering Application Manual T-030: Liquid Cooled Generator Sets
(A040S369)
2.5 Model Specifications
TABLE 1. MODEL VARIATIONS
Model
Natural Gas or
Propane Vapor
kW Amps Frequency Voltage
C13N6H Both 13 54.2
60 Hz
120/240 VAC
Single Phase
C17N6H Both 17 70.8
C20N6H,
C20N6HC
Natural Gas Only 18 75
Propane Vapor
Only
20 83.3
NOTICE
Maximum load imbalance allowed is 50% of generator set rating.
TABLE 2. COLD WEATHER REQUIREMENTS
Temperature Description
Above 4 °C (40 °F) No starting aids required
–17 to 4 °C (0 to 40 °F) Alternator heater
Below –17 °C (0 °F)
Alternator heater
0W30 oil (see the oil recommendation below)
Extreme cold weather kit (A054B984) (includes battery and
oil heaters)
TABLE 3. FUEL CONSUMPTION SPECIFICATIONS (AT FULL LOAD)
C13N6H C17N6H
C20N6H,
C20N6HC
Fuel Pressure
Type scfh BTU/hr scfh BTU/hr scfh BTU/hr kPa
in water
column
Natural Gas 228 217,200 258 246,000 268 256,000 0.9–3.0 3.5–12