Install Drawing

ECO-181860 Sheet 3 of 5
Part Name: A059K578 Revision: A
Drawing Name: A059K579 Revision: A
CKD
FIRST USED ON
FOR INTERPRETATION
OF DIMENSIONING AND
TOLERANCING, SEE
APVD
DWN
SIM TO
UNLESS OTHERWISE SPECIFIED, ALL
DIMENSIONS ARE IN MILLIMETERS
17.50-24.99 +0.30/-0.13
10.00-17.49 +0.25/-0.13
5.00- 9.99 +0.20/-0.10
0.00- 4.99 +0.15/-0.08
DIM
HOLE
ANG TOL
DO NOT SCALE PRINT
SCALE
SITE CODE
CUMMINS POWER GENERATION
SIZE
DWG
D
DATE
A059K578
6
5
4
3
2
1
D
C
B
A
6
5
4
3
2
1
D
C
B
A
PTC Creo Parametric
R
R
THIS DOCUMENT (AND THE INFORMATION SHOWN THEREON) IS
CONFIDENTIAL AND PROPRIETARY AND SHALL NOT BE DISCLOSED TO OTHERS
IN HARD COPY OR ELECTRONIC FORM, REPRODUCED BY ANY MEANS, OR
USED FOR ANY PURPOSE WITHOUT WRITTEN CONSENT OF CUMMINS INC.
R
OF
CAD SHEET
3 4
NO
REV
REL NO
DATE
APVD
CKD
DWN
REVISION
MINIMUM
UNOBSTRUCTED SPACE
762 30[ ]
MINIMUM TO
SURFACE/WALL
915 [36] MINIMUM
UNOBSTRUCTED SPACE
1524 60[ ]
MINIMUM TO
SURFACE/WALL
915 [36] MINIMUM
UNOBSTRUCTED SPACE
1524 60[ ]
MINIMUM
UNOBSTRUCTED SPACE
762 30[ ]
MINIMUM458 18[ ]
MINIMUM TO SURFACE/WALL
458 [18] MINIMUM UNOBSTRUCTED SPACE
1524 60[ ]
R MINIMUM AROUND
ENTIRE GENERATOR SET TO
ANY OPENING IN AN OCCUPIED
SPACE (WINDOWS, DOORS,
VENTS, ETC.)
1524 60[ ]
MINIMUM458 18[ ]
R MINIMUM AROUND
ENTIRE GENERATOR SET TO
ANY OPENING IN AN OCCUPIED
SPACE (WINDOWS, DOORS,
VENTS, ETC.)
1524 60[ ]
MINIMUM TO SURFACE/WALL
458 [18] MINIMUM UNOBSTRUCTED SPACE
1524 60[ ]
MINIMUM
TO SURFACE/WALL
1524 [60] MINIMUM TO ANY
OPENING IN AN OCCUPIED SPACE
1524 60[ ]
1
X #
0.8
.X #
0.38
.XX#
1.0 3/16 ARROW
ASME Y14.5-2009
27NOV18
D_GILLETT
D_GILLETT
R_MANE
OUTLINE,GENSET
ECO-181860 A 1 PRODUCTION_RELEASE RM DG
D_GILLETT
27NOV18
PGF
A053G027
SCALE 1/8
TOP OF GENERATOR SET
CIRCUIT
BREAKER
ENGINE
END
ALTERNATOR END
SURFACE/WALL
SURFACE/WALL
SCALE 1/8
TOP OF GENERATOR SET
CIRCUIT
BREAKER
ENGINE
END
ALTERNATOR END
SURFACE/WALL
SURFACE/WALL
SIDE OF GENERATOR SET
CLEARANCE REQUIREMENTS FOR
GENERATOR SET INSTALLATIONS
AIR FLOW
AIR FLOW
AIR FLOW