Spec Sheet

©2019 Cummins Inc. | NAS-6254-EN (A056T581) (10/19)
power.cummins.com
Specification sheet
Quiet Connect
TM
Series - RS13A,
RS17A, RS20A, &
RS20AC
Features and benefits
Robust Design – The generator is designed
to operate in cold weather with performance
down to 0 °F (-18 °C) out of the box. The
extreme cold weather models can perform
down to -40 °F (-40 °C) out of the box. It is
tested and certified per the latest EPA, UL,
and CSA standards. The generator meets
NFPA 37 which allows it to be installed 18
inches from a building. It has powerful motor
starting ability and can easily start and run a
5-ton A/C¹ under full pre-load.
Intelligent Load Management - The
generator can control up to 4 loads and
continuously monitors how much power is
required independently for each load. It then
controls each load for maximum utilization of
generator power by only restoring loads the
generator has capacity to run.
Flexible Exercise Modes - Exercise modes
can be set for time, date, and frequency that
suits the owner. Our patented ‘Crank only’
exercise mode allows the generator to crank
the engine and run diagnostics without
starting the engine. This reduces wear and
tear on the engine, fuel costs, and further
reduces the sound of an already quiet
generator.
Remote Monitoring - Remote monitoring is
built into every generator. Using a computer,
tablet, or smart phone, an operator can
monitor, change exercise modes, and
manually run the generator remotely.
Generator and ATS packaged sets
– The
RS20AC comes with a 20-kW generator and
200A service entrance rated ATS in one box
to make ordering more convenient.
Weight, size and sound level
Size:
Length: 34.1 in (865 mm), Width: 36.0 in (915 mm), Height: 27.3 in (694 mm)
Sound: 65 dB(A) at 23 ft. (7 m) at normal load
2
Voltage / Frequency
: 120/240V / 60Hz
Series Model Part number
Extreme Cold
Weather
Rated amp
3
(NG / LPV)
Weight
Lbs. / Kg
RS13A C13N6H A061C591 No 54.2 / 54.2 479 / 217
RS17A C17N6H A061C596 No 70.8 / 70.8 531 / 241
RS20A C20N6H A061C601 No 75 / 83.3 531 / 241
RS20AC C20N6HC A061C602 No 75 / 83.3 596 / 271
RS13AE C13N6H A062E510 Yes 54.2 / 54.2 479 / 217
RS17AE C17N6H A062E511 Yes 70.8 / 70.8 531 / 241
RS20AE C20N6H A062E512 Yes 75 / 83.3 531 / 241
RS20ACE C20N6HC A062E513 Yes 75 / 83.3 596 / 271
¹
Air-conditioners vary by type, operational conditions, etc. Consult with a qualified Cummins Power Generation distributor/dealer for
proper sizing.
²
Quietest point at a normal load. Sound performance may be affected by installation.
³ Derating guidelines: Maximum wattage or maximum current are subject to and limited by such factors as fuel Btu content,
ambient
temperature, altitude, engine power and condition, etc. Full rated power available up to the following, derate 3.5% for each increase of
300 m (1000 ft.) and 1% for each increase of 5.5 °C (10 °F) after that:
RS20A & R20AC – at 15 °C (60 °F) and 0 m (0 ft.).
RS17A - at 25 °C (77 °F) and 300 m (1000 ft.)
RS13A
at 25 °C (77 °F) and 2100 m (6900 ft.)

Summary of content (5 pages)