Service Manual

Table Of Contents
4. Operation 10-2019
54 A062J683 (Issue 1)Copyright © 2019 Cummins Inc.
4. After the generator set reaches rated voltage and frequency, the transfer switch
transfers the building load to the generator set (unless the circuit breaker on the
generator set is "off"). The building's electrical power is now provided by the
generator set.
FIGURE 25. GENSET POWER
4.5 Manual Stop Sequence (Local)
The following steps will be executed when Manual Stop is selected at the Local
display:
1. Press the red STOP button on the local display. The generator set will stop
immediately and the building load will be transferred to the utility.
2. For normal operation to resume, Standby will need to be enabled. See the
section on enabling Standby Mode.
NOTICE
The red STOP button on the Local display, when pressed, will cause
both Remote and Standby Modes to be disabled.
4.6 Manual Start/Stop Sequence (Remote)
Remote mode must be enabled on the local display to allow manual start and stop
from the Remote display. The manual start and stop sequences are the same for
the Remote display and the Local display.
NOTICE
The red STOP button on the Remote display, when pressed, will cause the
Standby Mode to be disabled.
4.7 "Fault" and "New Event" Screens
Various fault and event screens may appear on the operator display.
"FAULT" SCREEN