Service Manual
Table Of Contents
- Table of Contents
- 1. IMPORTANT SAFETY INSTRUCTIONS
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 Generator Set Safety Code
- 1.4 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.5 Fuel and Fumes Are Flammable
- 1.6 Exhaust Gases Are Deadly
- 1.7 The Hazards of Carbon Monoxide
- 1.8 Earth Ground Connection
- 2. Introduction
- 3. Startup
- 4. Operation
- 5. Maintenance
- 5.1 Maintenance Safety
- 5.2 Periodic Maintenance
- 5.3 Engine Oil
- 5.4 Engine Valve Clearance
- 5.5 Normal Duty Air Cleaner Element Replacement
- 5.6 Exhaust System Maintenance
- 5.7 DC Electrical System
- 5.8 Batteries
- 5.9 Spark Plugs
- 5.10 Cleaning the Generator Set Housing
- 5.11 Cleaning the Slip Rings
- 5.12 Exercising the Generator Set
- 5.13 Complete System Test
- 6. Service
- 7. Troubleshooting
- 7.1 Troubleshooting Procedures
- 7.2 Safety Considerations
- 7.3 GATRR Troubleshooting Approach
- 7.4 Tools and Parts Required
- 7.5 Troubleshooting with the Local or Remote Displays
- 7.6 Utility-Powered Battery Charger Troubleshooting
- 7.7 Engine Flywheel Battery Charger Troubleshooting
- 7.8 Fuel Shutoff Solenoid Valve
- 7.9 Compression Test Procedure
- 7.10 Connecting with the InPower Service Tool
- 7.11 Troubleshooting by Symptom
- 7.12 Troubleshooting with Fault Codes
- 7.13 Remote Monitoring Communication Troubleshooting
- Appendix A. Wiring Diagrams
6. Service 10-2019
130 A062J683 (Issue 1)Copyright © 2019 Cummins Inc.
• One set of two leads from the customer wiring that is installed in the lugs at
the bottom of the breaker (L1 and L2)
3. Check continuity as follows:
• When the breaker is on (that is, the contacts inside the breaker are closed),
the continuity check should show very low resistance between the pair of
L1 lugs and the pair of L2 lugs.
• When the breaker is off (that is, the contacts inside the breaker are open),
the continuity check between L1 and L2 pairs should show open.
The breaker should be replaced if either of the continuity tests fail.