Operator Quick Start Guide
A062M461
SAFETY PRECAUTIONS
Thorough understanding of the operator manual and health and safety manual is necessary before operating the generator set. Safe
operation and proper performance can only be obtained when the generator set is operated and maintained properly.
PRE-START CHECKLIST
Generator set engine is properly serviced with oil.
All generator set covers and safety shields are installed correctly.
All fuel shutoff valves are operational and in the open position.
The installation is compliant with state and local codes and regulations.
Remove any debris that has accumulated around the generator set.
SELECTING AN OPERATING MODE
Note: When changing operating modes, the generator set can start or stop without warning (for example, if Standby mode is
selected and utility power is not connected, the generator set will attempt to start). Make sure there is no danger to personnel or
equipment if the generator set starts or stops.
SETTING THE REMOTE AND STANDBY MODES
Enable/Disable Remote or Standby (Local Display)
Enable/Disable Standby (Remote Display)
1. From any screen, select the Mode key to get to the Mode
screen.
2. Use the arrow keys to enable or disable the Remote mode.
Select the Next key to go to the next screen.
3. Use the arrow keys to enable or disable the Standby mode.
4. Whenever Standby is enabled, the Remote mode will also
automatically be enabled.
5. Keep pressing the Back button to save the settings and return
to the Main screen.
1. From any screen, select the Mode key to get to the
Mode screen.
2. Use the arrow keys to enable or disable the Standby
mode. (Local display needs to be in remote to
enable or disable Standby.)
3. Keep pressing the Back button to save the settings
and return to the Main screen.
BASIC SEQUENCE OF OPERATION
When the generator set is equipped with a transfer switch and the generator set is in Standby mode:
Utility power goes out:
1. The generator set starts.
2. After the generator set reaches rated voltage and frequency, the transfer switch transfers the
building load to the generator set. The building's electrical power is now provided by the generator
set.
Utility power returns:
1. The sequence to transfer building load to the utility begins.
2. The generator set continues to run and waits for utility power to stabilize.
3. When utility power is stable for 5 minutes, the transfer switch connects the building load back to
utility power.
4. The generator set runs an additional 5 minutes to cool down and then shuts off.
5. Normal operation resumes.
EXERCISING THE GENERATOR SET
When in the Standby mode, the generator set will exercise at the scheduled time for the duration set in the generator set control or
transfer device. Refer to the operator manual to understand and/or modify the settings for the exercising schedule.
Note: Crank exercise is enabled as a default. During every other exercise cycle the generator will not start. See the Operator manual
to disable.