5. Maintenance 8-2019
76 A062J680 (Issue 2)Copyright © 2019 Cummins Inc.
20. Reconnect the cables and battery charger:
a. Reconnect the engine battery cables, positive (+) cable first.
b. Reconnect the battery charger to its AC power source.
21. Reconnect the oil heater AC power or energize its AC circuit.
22. Operate the generator set with no load for approximately 5 minutes to check for
leaks at the oil filter or oil drain hose.
23. Shut down the generator set, wait 5 minutes, and then confirm that the correct
oil level is in the pan.
24. Check for leaks and repair any that are identified.
25. Dispose of the used oil and oil filter according to local environmental
regulations.
26. Re-install the access panels. Torque the fasteners 5.0–6.6 Nm (3.5–5.0 ft-lb).
27. Restore the original generator set settings.
28. Close the generator set breaker.
5.4 Normal Duty Air Cleaner Element Replacement
NOTICE
Cummins Inc. does not recommend cleaning paper-type air cleaner
elements.
AIR CLEANER ELEMENT REMOVAL
1. Make sure the generator set is shut down and disabled:
a. Press the generator set's red STOP button on the local display to stop the
generator set. Allow the generator set to thoroughly cool to the touch.
b. Turn off and disconnect the battery charger from the AC source before
disconnecting the battery cables.
c. Disconnect the negative (–) cable from the battery and secure it from
contacting the battery terminals to prevent accidental starting.
WARNING
Automatic startup of the generator set during maintenance can cause
severe personal injury or death.
2. Remove the access cover to get to the air cleaner housing.
3. Wipe away any debris accumulated on the air cleaner housing.
4. Remove the two M6 pan head screws.