Product Manual

3. Control System 8-2019
36 A062J680 (Issue 2)Copyright © 2019 Cummins Inc.
"Mode" Screen
When Remote is set to Enabled via the local display, the “Remote On” LED on the
front of the display will illuminate indicating that the control will accept start
commands from remote displays or remote monitoring systems including a web
page or cell phone app.
NOTICE
The Remote function can only be activated (that is, enabled) from the local
display.
When Standby is on or set to Enabled, the “Standby On” LED on the front of the
display will illuminate indicating the control will start the generator set in response to
a utility power outage. Standby can be turned on at the local display. It can also be
enabled with a remote display, web page, or a cell phone app if Remote has already
been enabled at the local display. The Standby function cannot be enabled
remotely unless the Remote function is on. A manual Start or Stop event will disable
the Standby function. (If the manual Stop event is performed at the local display, the
Remote mode will also be disabled.)
1. To enable or disable the Remote and Standby modes on the LOCAL display,
do the following:
a. From any screen, select the Mode key to get to the Mode screen.
b. Use the arrow keys to enable or disable the Remote mode. Select the Next
key to go to the next screen.
c. Use the arrow keys to enable or disable the Standby mode.
NOTICE
Whenever Standby is enabled, the Remote mode will also
automatically be enabled.
d. Keep pressing the Back button to save the settings and return to the Main
screen.