Product Manual
Table Of Contents
- Table of Contents
- 1. IMPORTANT SAFETY INSTRUCTIONS
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 Generator Set Safety Code
- 1.4 Moving Parts Can Cause Severe Personal Injury or Death
- 1.5 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.6 Fuel and Fumes Are Flammable
- 1.7 Batteries Can Explode
- 1.8 Exhaust Gases Are Deadly
- 1.9 The Hazards of Carbon Monoxide
- 1.10 Earth Ground Connection
- 2. Introduction
- 3. Control System
- 4. Operation
- 5. Maintenance
- 6. Troubleshooting
2. Introduction8-2019
17A062J680 (Issue 2) Copyright © 2019 Cummins Inc.
TABLE 6. GENERATOR SET WET WEIGHT (INCLUDING BATTERY)
Model Value
C13N6H 218 kg (479 lb)
C17N6H, C20N6H, C20N6HC 241 kg (531 lb)
TABLE 7. GENERATOR SET DERATING GUIDELINES
Model
Engine Power Available Up To... Derate At…
Elevation Ambient Temperature Elevation Temperature
C13N6H 2100 m (6900 ft) 25 °C (77 °F)
3.5% per
300 m
(1000 ft)
1% per
5.5 °C (10 °F)
C17N6H 300 m (1000 ft) 25 °C (77 °F)
C20N6H,
C20N6HC
0 m (0 ft) 15 °C (60 °F)
NOTICE
Derating guidelines: This product's output power is limited by factors such
as BTU content of fuel, ambient temperature, altitude, humidity, engine
condition, etc. The derating guidelines are based on properly maintained
product, using the appropriate fuel. Derate values are based on expected
engine power changes from elevation and temperatures listed.
TABLE 8. ALTERNATOR SPECIFICATIONS
Type Specification
Design Rotating field
Poles 2
RPM 3600
Voltage 240
Hz 60
TABLE 9. CONTROL SPECIFICATIONS
Control
Integrated Microprocessor-Based Engine, Alternator, Transfer Switch Controller