Install Manual

4. Installation 8-2019
38 A062J678 (Issue 2)Copyright © 2019 Cummins Inc.
Converting the Fuel System Type
The generator set leaves the factory set up for natural gas. For operation on
liquid propane vapor, the generator set must be converted by configuring the
generator set control for propane and manually changing the fuel valve
position from natural gas to propane.
1. To change the generator set control's fuel type from natural gas to liquid
propane vapor:
a. From the Main screen, select Menu.
b. Press and hold the Next key on the Menu screen for at least 5
seconds to view the Config Menu.
c. Use the arrow keys to highlight "Config" and click the Enter key. The
Generator Config screen appears.
d. Use the Next key to navigate to the Fuel Type field. Use the arrow
keys to select the fuel type: NG (natural gas; default) or LP (liquid
propane).
NOTICE
Do not change the number in the Config field.
NOTICE
The Rating field is not configurable by the user. Instead, it will
be automatically populated based on the Config and Fuel Type
field selections.
e. Keep selecting the Back button to save the settings and return to the
Main screen.