Install Manual
Table Of Contents
- Table of Contents
- 1. Important Safety Instructions
- 1.1 Save These Instructions
- 1.2 General Information
- 1.3 General Precautions
- 1.4 Generator Set Voltage Is Deadly
- 1.5 Engine Exhaust Is Deadly
- 1.6 Fuel and Fumes Are Flammable
- 1.7 Batteries Can Explode
- 1.8 Starting Batteries
- 1.9 Moving Parts Can Cause Severe Personal Injury or Death
- 1.10 The Hazards of Carbon Monoxide
- 2. Introduction
- 3. Pre-Installation Considerations
- 4. Installation
- 5. Startup and Configuration
- 5.1 "Establishing Communications" Message
- 5.2 "Clock Setup" Screen
- 5.3 "Exercise" Screen
- 5.4 "Brightness and Contrast" Screen
- 5.5 "About" Screen
- 5.6 "Event Log" Screen
- 5.7 "Fault Log" Screen
- 5.8 "System Status" Screen
- 5.9 "Mode" Screen
- 5.10 Automatic Load Management
- 5.11 Manual Start Sequence (Local)
- 5.12 Checklist
- 5.13 Startup
- 6. Remote Monitoring System (RMS) Description
- Appendix A. Fuel Line Selection
- Appendix B. Outline and System Drawings
- Appendix C. Wiring Diagrams
2. Introduction 8-2019
16 A062J678 (Issue 2)Copyright © 2019 Cummins Inc.
2.5 Before Installation
Before beginning the installation of the generator set, verify that the unit was
correctly selected. Check the following features:
• Model
• Specifications
• Options
• Fuel Supply
◦ The gas supplied to the generator set must be of acceptable quality.
◦ The gas supply must have sufficient pressure. Care must be taken to be
sure that the gas supply at the generator set, not just at the source, is of
proper pressure for operation. The specified pressure must be available
while the generator set is starting and running at full load.
◦ The gas must be supplied to the generator set in sufficient volume to
support operation of the generator set. This is normally a matter of
selecting fuel line size to be large enough to transport the volume of fuel
needed. For liquid propane vapor-withdrawal fuel systems the size and
temperature of the fuel tank also affects this requirement.