Service Manual
Table Of Contents
- Table of Contents
 - 1. IMPORTANT SAFETY INSTRUCTIONS
- 1.1 Warning, Caution, and Note Styles Used in This Manual
 - 1.2 General Information
 - 1.3 Generator Set Safety Code
 - 1.4 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
 - 1.5 Fuel and Fumes Are Flammable
 - 1.6 Exhaust Gases Are Deadly
 - 1.7 The Hazards of Carbon Monoxide
 - 1.8 Earth Ground Connection
 
 - 2. Introduction
 - 3. Startup
 - 4. Operation
 - 5. Maintenance
- 5.1 Maintenance Safety
 - 5.2 Periodic Maintenance
 - 5.3 Engine Oil
 - 5.4 Engine Valve Clearance
 - 5.5 Normal Duty Air Cleaner Element Replacement
 - 5.6 Exhaust System Maintenance
 - 5.7 DC Electrical System
 - 5.8 Batteries
 - 5.9 Spark Plugs
 - 5.10 Cleaning the Generator Set Housing
 - 5.11 Cleaning the Slip Rings
 - 5.12 Exercising the Generator Set
 - 5.13 Complete System Test
 
 - 6. Service
 - 7. Troubleshooting
- 7.1 Troubleshooting Procedures
 - 7.2 Safety Considerations
 - 7.3 GATRR Troubleshooting Approach
 - 7.4 Tools and Parts Required
 - 7.5 Troubleshooting with the Local or Remote Displays
 - 7.6 Utility-Powered Battery Charger Troubleshooting
 - 7.7 Engine Flywheel Battery Charger Troubleshooting
 - 7.8 Fuel Shutoff Solenoid Valve
 - 7.9 Compression Test Procedure
 - 7.10 Connecting with the InPower Service Tool
 - 7.11 Troubleshooting by Symptom
 - 7.12 Troubleshooting with Fault Codes
 - 7.13 Remote Monitoring Communication Troubleshooting
 
 - Appendix A. Wiring Diagrams
 
2. Introduction10-2019
17A062J683 (Issue 1) Copyright © 2019 Cummins Inc.
• RA Series Automatic Transfer Switch Owner Manual (A046S594) (models
RA112N3, RA212N3, RA112S3, RA212S3, RA412N3, and RA412S3) - if
applicable
• Parts Manual (A053X179)
• Standard Repair Times - HO Family (A053X186)
• Service Tool Manual (A043D529)
• Warranty Failure Code Manual (F1115C)
• Engineering Application Manual T-030: Liquid Cooled Generator Sets
(A040S369)
2.5 Model Specifications
TABLE 1. MODEL VARIATIONS
Model
Natural Gas or
Propane Vapor
kW Amps Frequency Voltage
C13N6H Both 13 54.2
60 Hz
120/240 VAC
Single Phase
C17N6H Both 17 70.8
C20N6H,
C20N6HC
Natural Gas Only 18 75
Propane Vapor
Only
20 83.3
NOTICE
Maximum load imbalance allowed is 50% of generator set rating.
TABLE 2. COLD WEATHER REQUIREMENTS
Temperature Description
Above 4 °C (40 °F) No starting aids required
–17 to 4 °C (0 to 40 °F) Alternator heater
Below –17 °C (0 °F)
• Alternator heater
• 0W30 oil (see the oil recommendation below)
• Extreme cold weather kit (A054B984) (includes battery and
oil heaters)