Spec Sheet
©2019 Cummins Inc. | NAS-6254-EN (A056T581) (10/19)
  power.cummins.com 
Specification sheet
Quiet Connect
TM
Series - RS13A, 
RS17A, RS20A, & 
RS20AC 
Features and benefits 
Robust Design – The generator is designed 
to operate in cold weather with performance 
down to 0 °F (-18 °C) out of the box. The 
extreme cold weather models can perform 
down to -40 °F (-40 °C) out of the box. It is 
tested and certified per the latest EPA, UL, 
and CSA standards. The generator meets 
NFPA 37 which allows it to be installed 18 
inches from a building. It has powerful motor 
starting ability and can easily start and run a 
5-ton A/C¹ under full pre-load. 
Intelligent Load Management - The 
generator can control up to 4 loads and 
continuously monitors how much power is 
required independently for each load. It then 
controls each load for maximum utilization of 
generator power by only restoring loads the 
generator has capacity to run. 
Flexible Exercise Modes - Exercise modes 
can be set for time, date, and frequency that 
suits the owner. Our patented ‘Crank only’ 
exercise mode allows the generator to crank 
the engine and run diagnostics without 
starting the engine. This reduces wear and 
tear on the engine, fuel costs, and further 
reduces the sound of an already quiet 
generator. 
Remote Monitoring - Remote monitoring is 
built into every generator. Using a computer, 
tablet, or smart phone, an operator can 
monitor, change exercise modes, and 
manually run the generator remotely. 
Generator and ATS packaged sets 
– The 
RS20AC comes with a 20-kW generator and 
200A service entrance rated ATS in one box 
to make ordering more convenient. 
Weight, size and sound level 
Size:
 Length: 34.1 in (865 mm), Width: 36.0 in (915 mm), Height: 27.3 in (694 mm) 
Sound: 65 dB(A) at 23 ft. (7 m) at normal load
2 
Voltage / Frequency
: 120/240V / 60Hz 
Series  Model  Part number 
Extreme Cold 
Weather 
Rated amp
3
(NG / LPV) 
Weight 
Lbs. / Kg 
RS13A  C13N6H  A061C591  No  54.2 / 54.2  479 / 217 
RS17A  C17N6H  A061C596  No  70.8 / 70.8  531 / 241 
RS20A  C20N6H  A061C601  No  75 / 83.3  531 / 241 
RS20AC  C20N6HC  A061C602  No  75 / 83.3  596 / 271 
RS13AE  C13N6H  A062E510  Yes  54.2 / 54.2  479 / 217 
RS17AE  C17N6H  A062E511  Yes  70.8 / 70.8  531 / 241 
RS20AE  C20N6H  A062E512  Yes  75 / 83.3  531 / 241 
RS20ACE  C20N6HC  A062E513  Yes  75 / 83.3  596 / 271 
¹
 Air-conditioners vary by type, operational conditions, etc. Consult with a qualified Cummins Power Generation distributor/dealer for 
proper sizing. 
² 
Quietest point at a normal load. Sound performance may be affected by installation. 
³ Derating guidelines: Maximum wattage or maximum current are subject to and limited by such factors as fuel Btu content, 
ambient 
temperature, altitude, engine power and condition, etc. Full rated power available up to the following, derate 3.5% for each increase of 
300 m (1000 ft.) and 1% for each increase of 5.5 °C (10 °F) after that: 
RS20A & R20AC – at 15 °C (60 °F) and 0 m (0 ft.). 
RS17A - at 25 °C (77 °F) and 300 m (1000 ft.) 
RS13A 
–
at 25 °C (77 °F) and 2100 m (6900 ft.)