4. Installation3-2016
39A051X873 (Issue 5) Copyright © 2016 Cummins Inc.
NOTICE
The CCV heater requires power from a 120 VAC, 20 Amp protected
circuit from the Main Distribution Panel. The CCV needs to be powered
even during utility outages. Use 12 AWG 167 °F (75 °C) conductors to
connect to the generator set AC distribution connector.
FIGURE 10. AC ACCESSORY CONNECTIONS