Install Manual
Table Of Contents
- Table of Contents
 - 1. Important Safety Instructions
- 1.1 Warning, Caution, and Note Styles Used in This Manual
 - 1.2 General Information
 - 1.3 General Precautions
 - 1.4 Generator Set Voltage Is Deadly
 - 1.5 Engine Exhaust Is Deadly
 - 1.6 Fuel and Fumes Are Flammable
 - 1.7 Batteries Can Explode
 - 1.8 Moving Parts Can Cause Severe Personal Injury or Death
 - 1.9 The Hazards of Carbon Monoxide
 
 - 2. Introduction
 - 3. Pre-Installation Considerations
 - 4. Installation
 - 5. Startup and Configuration
 - Appendix A. Fuel Line Selection
 - Appendix B. Outline and System Drawings
 - Appendix C. Seismic Requirements
 
Appendix A. Fuel Line Selection 2-2016
80 A045R241 (Issue 7)Copyright © 2016 Cummins Inc.
Equivalent
Length
of Pipe (ft.)
Schedule 40 Iron Pipe Size (in.): Nominal (Inside Diameter)
1/2
(0.622)
3/4
(0.824
)
1
(1.049)
1 1/4
(1.38)
1 1/2
(1.61)
2
(2.067)
3
(3.068
)
3 1/2
(3.548)
4
(4.026
)
900 116 243 458 941 1,409 2,715 7,649 11,199 15,60
1
1000 110 230 433 889 1,331 2,564 7,225 10,579 14,73
7
1500 88 184 348 713 1,069 2,059 5,802 8,495 11,83
4
2000 76 158 297 611 915 1,762 4,966 7,271 10,12
8
*Pipe size recommendations are based on schedule 40 black iron pipe.
FIGURE 27. MINIMUM LPG TANK SIZE (50% FULL) REQUIRED TO MAINTAIN 5 PSIG
AT SPECIFIC WITHDRAWAL RATE AND MINIMUM EXPECTED WINTER TEMPERATURE