Product Manual
Table Of Contents
Page 5 of 17A045H700 (Issue 5) Copyright © 2017 Cummins Inc.
TABLE 1. GENERATOR SET MODELS
Type Models
Generator sets with a
display panel knockout
C20 N6, C22 N6, C25 N6, C30 N6, C36 N6, C40 N6, C30 N6H, C36 N6H, C40 N6H,
C45 N6H, C50 N6H, C60 N6H, C10 D6, C15 D6, C20 D6, C25 D6, C30 D6, C35 D6,
C40 D6, C50 D6, and C60 D6
Generator sets with a
display panel rubber plug
C45 N6, C50 N6, C60 N6, C70 N6, C80 N6, C100 N6, C50D6C, C60D6C, C80D6C,
C100D6C, C125D6C, C125 N6, C150 N6, C125D6D, C150D6D, C175D6D, C200D6D,
C230D6D, and C250D6D
Generator sets that require
hole drilling
C13N6H, C17N6H, C20N6H, and C20N6HC
Because the installation presents a severe shock hazard, this kit must be installed by trained and
experienced personnel only.
Read these instructions completely and become familiar with safety warnings, cautions and procedures
before starting the installation.
NOTICE
The generator set will be inoperable during the installation of this kit. Be sure to notify all
potentially affected individuals before beginning work.
NOTICE
Before servicing the PCC, it is recommended that all settings be recorded. This will ensure
correct and complete readjustment of the PCC if all previous entries are lost during servicing.
1. Make sure the generator set is shut down and disabled.
a. Turn the generator set off:
• Generator sets with a display panel knockout or rubber plug only: Press the generator
set's PCC "O" (Off) button on the local display to stop the generator set.
• Generator sets that require hole drilling only: Press the generator set's red Stop button on
the local display to stop the generator set. Be sure to note the generator settings.
b. Allow the generator set to cool thoroughly to the touch.
c. Turn off and disconnect the battery charger from the AC source before disconnecting the
battery cables (if applicable).
d. Disconnect the negative (-) cable from the battery and secure it from contacting the battery
terminals to prevent accidental starting.
2. Remove the roof panel (dome) on the set (if applicable).
3. Generator sets with a display panel knockout or rubber plug only: Remove the display panel (shown
in the figures below).